How to work out the static pressure your fan needs

Alfotech engineering team November 26, 2026

Every fan enquiry needs two numbers: how much air, and against how much resistance. The second number is the static pressure, and it is the one most often guessed. A fan chosen for too little pressure simply will not deliver its air flow once it is connected to the system.

What static pressure is

Air moving through hoods, ducts, bends, filters and collectors loses pressure to friction and turbulence. The fan has to make up all of those losses. Add them together along the path the air takes, and you have the static pressure the fan must develop at your air flow.

Add up the losses along one path

  • Hood or inlet. Air accelerating into a hood loses pressure. A plain opening loses more than a flanged or bell-mouth inlet.
  • Straight duct. Friction loss depends on the length, the diameter and the air velocity. Halving the diameter at the same flow raises the loss many times over.
  • Bends and branches. Each fitting adds a loss. Sharp bends and tees cost far more than long-radius bends and angled branch entries.
  • Equipment. Cyclones, scrubbers, filters, heat exchangers and dampers each have a pressure drop at their design flow. Take it from the maker's data.
  • Discharge. A stack, a weather cowl or a discharge into a pressurised space adds to the total.

Where the system has branches, follow the path with the highest total loss. The other branches are then balanced to it with dampers.

Pressure rises with the square of the flow

System resistance is not a fixed number. If you push 10% more air through the same ducts, the pressure loss rises by about 21%. This is why a fan and a system always settle at the point where the fan curve crosses the system curve, and why a small error in estimated pressure moves the air flow you actually get.

Common mistakes

  • Forgetting the collector or filter, which is often the largest single loss.
  • Using the pressure drop of a clean filter when it will run loaded most of the time.
  • Putting a bend directly on the fan inlet or outlet. Disturbed flow at the fan costs performance that no calculation shows.
  • Adding a large "safety margin" to the pressure. An oversized fan then has to be throttled, wasting power for its whole life.

If you do not have the numbers

Send a sketch of the duct layout with lengths, diameters and the equipment in the line. We can work out the pressure with you before selecting the fan.